Configurator – PID Loop Setup menu option

Prop Band (0 for On/Off)
This is the proportional band field. The range 0 – 999.0

Reset
This is the reset field. The range 0 – 100.00

Rate
This is the rate field. The range is 0 – 100.00. The rate is not typically used for heating/carbon

Mode
This is the mode of the loop. The values are: Dual Reverse, Single Reverse, Dual Direct,
or Single Direct.

Integral Preset
This field provides an offset for the starting point for PID control, also referred to as “Load Line”
or “Manual Reset”. The range is –100 to 100.

Cycle Time
This field is typically set to the valve travel time multiplied by 1.5.

Setpoint Change Limit
This is a smart time feature that allows Process Loop to use PB only without Reset until the
Process Variable drops below the percent output set under this category.
It is used to eliminate overshoot.
The Output percentage selected under this category

must

be above the normal operating

output percentage of the furnace at heat.