Super Systems PC Configurator 2 User Manual

Page 128

Advertising
background image

Super Systems Inc.

Page 128 of 201

Configurator Manual #4562 Rev D

Configurator – User Calibration screen 3


Calibrate the zero/span range for input 2 and click on the Next -> button to continue to the
fourth screen. Clicking on the <- Back button will display the previous screen.

Configurator – User Calibration screen 4

Calibrate the zero/span range for input 3 and click on the Next -> button to continue to the
fifth screen. Clicking on the <- Back button will display the previous screen.

Configurator – User Calibration screen 5


To calibrate the zero/span range for output 1, you must first attach your measuring device,
then select prep for Zero. Let the unit output what it has set for the zero measurement, then
enter what you are measuring coming out of the terminals. Once entered select Calibrate and
let the procedure finish. This will be the same for the Span output. Then click on the Next ->
button to continue to the sixth screen. Clicking on the <- Back button will display the previous
screen.