Example – if the furnace runs at 40% output at heat for the maximum load, the setpoint
change limit should be set to 60%.

Low Limit
This is the low limit field. The range is –100 to 100.

High Limit
This is the high limit field. The range is –100 to 100.

0 Setpoint Stops Control
If the Setpoint is zero, then all outputs are turned off. The option is either Yes or No.

IN1 high limit shuts down ctrl
If input 1’s high limit is reached, then all outputs are turned off. The value can either be Yes or
No.

IN2 high limit shuts down ctrl
If input 2’s high limit is reached, then all outputs are turned off. The value can either be Yes or
No.

IN3 high limit shuts down ctrl
If input 3’s high limit is reached, then all outputs are turned off. The value can either be Yes or
No.

PID Auto Switch

This is the PID auto switch field. The value can either be Yes or No.

Switch Point PID 1 -> 2
This is the PID Switch Point field. The range is –300 to 4000.

Switch Point PID 2 -> 3
This is the PID Switch Point field. The range is –300 to 4000.

Overshoot Limit Gain
This is the Overshoot limit gain field. The range is 0 to 9999.

Reset Limiter
This is the reset limiter field. The values can either be On or Off.

Factory Default Configuration:

Carbon:
Loop 1 Prop Band (DB ON/ OFF)

20.0

LP 1 Reset

0.10

LP 1 Rate

0.00

LP 1 Mode

Dual Reverse

LP 1 Integral Preset

0

LP 1 Cycle Time

16