Configurator – SSi Configuration and Calibration menu option


Overview
The series 9200 can be calibrated using the operator interface Configurator software usually
supplied with the system. Before performing this procedure on a newly installed controller, the
unit needs to be powered on for at least 30 minutes for a warm up period.
The series 9200 has three analog inputs. Each range has a zero and span calibration value. A
cold junction trim value must be calibrated for thermocouple inputs. There are two analog
outputs each with a zero and span value.

When using the User Calibration procedure this will

allow for the user to only calibrate the input ranges being used in the controller for which ever
specific PVT is selected under furnace setup. The Full Calibration will calibrate all of the input
ranges regardless of what is selected for PVT.

Equipment needed
A certified calibrator(s) with the ability to input and read millivolts, milliamps and thermocouples
is required. The appropriate connection leads are also required. A 24VDC 75-watt power supply
is required. The operator interface method requires a PC with the Configurator software loaded.
An Ethernet crossover cable is required.

Notes
Input 1 – terminals 31 and 32
Input 2 – terminals 29 and 30
Input 3 – terminals 27 and 28
Output 1 – terminals 24 and 25
Output 2 – terminals 25 and 26