Aux Setpoint Configuration

Configurator – Aux Setpoint Configuration menu option


See the menu option

Slave Instruments

for configuration prior to using

Aux Setpoint

Configuration

. This menu option allows for up to 3 slave instruments to have the setpoint

retransmitted from one of the three control loops. This menu option is typically used to
retransmit an alarm setpoint value to an overtemp controller.

Offset:
Carbon - 1 = 0.01
Temperature – 1 = 1

Delay:
This is measured in seconds
Clicking on the values for “Retrans To Slave 1”, “Retrans to Slave 2”, or “Retrans to Slave 3” will
display an input box with a drop-down list from which the user can select the new value. The
options are:
Off
Loop

1

Loop

2

Loop

3


Clicking on any of the values for “Setpoint Offset SI 1”, “Setpoint Offset SI 2”, “Setpoint Offset
SI 3”, “Setpoint Delay SI 1”, “Setpoint Delay SI 2”, or “Setpoint Delay SI 3” will display an input
box from which the user can select the new value. The range is –32768 to 32767.