Tolerance Band:
This is the tolerance band for the thermocouple. The range is –9999 to 9999.

Source 2 Offset:
This is the offset for source 2. The range is –9999 to 9999.

Source 3 Offset:
This is the offset for source 3. The range is –9999 to 9999.

Relay Assignments

Configurator – Relay Assignments menu option


The 9220 controller has the option of using eight relay outputs. All of the relays have a positive
common terminal and independent negative terminals. All of the relays are configured in a
normally closed position except relay number eight, which has both a normally closed (NC) and
a normally open (NO) terminal.

Relay Output Terminals:
Relay Output 1 – terminals 7 and 8
Relay Output 2 – terminals 7 and 9
Relay Output 3 – terminals 7 and 10
Relay Output 4 – terminals 7 and 11
Relay Output 5 – terminals 7 and 12
Relay Output 6 – terminals 7 and 13
Relay Output 7 – terminals 7 and 14
Relay Output 8 – terminals 7 and 15 NC
Relay Output 8 – terminals 7 and 16 NO

Relay Output Choices:
Loop1

fwd

Event

15

event

27

Loop1 rev

Out gas hold

event 28