Wiring of the standard device

Standard devices in the power range 0.37 ... 11 kW

Mains connection, DC supply

5

5.4

5.4.3

l

5.4−5

EDSVS9332K EN 8.0−07/2013

L1 L2 L3 +UG -UG

PE

L1, L2, L3
+U , -U

G

G

0.5...0.6 Nm
4.4...5.3 lb-in

2

0
1

9300std033

Fig. 5.4−3

Mains connection, DC supply for drive controllers 0.37 ... 11 kW

0 Mains cable

1 Shield sheet

Securely clamp mains cable with the lugs

2 Mains and DC bus connection

L1, L2, L3: Connection of mains cable
+U

G

, −U

G

: Connection of DC−bus components or connection of the controller

in the DC−bus system (see system manual)
Cable cross−sections up to 4 mm

2

: Use wire end ferrules for flexible cables

Cable cross−sections > 4 mm

2

: Use pin−end connectors

Mains connection, DC supply