Troubleshooting and fault elimination, Error messages during profile download – Lenze EVS9332xK User Manual

Page 409

Advertising
background image

Troubleshooting and fault elimination

Error messages during profile download

9

9.4

l

9.4−3

EDSVS9332K EN 8.0−07/2013

Remedy

Cause

Fault name

Code

C0397/x

INV_COLLISION_
RANGE

Online access not enabled.

Set code C0389/0 = 1.

C0398/x

C0399/x

C0501/1

Check X values (ascending order)

INV_VALUE_RANGE

The X values are not in
ascending order.

Check source data and repeat transfer.

C0502/1

Profile selection

INV_COLLISION_
RANGE

Attempt to write to a
non−existing profile.

Read out the maximum number of existing profiles from code
C0390/0.

C0504/2

Write data field as an *.LC7 file

INV_LENGTH_RANGE Attempt to write beyond the

data field.

l

Limit the number of writing cycles.

l

Set the pointer to the beginning of the data field
(C0505/2 = 0)

C0504/3

Write the X values in increments with automatic indexing of the address pointer (auto−increment)

INV_LENGTH_RANGE Attempt to write beyond the

data field.

l

Limit the number of writing cycles to the existing number of
interpolation points (see C0391/x).

l

Set the pointer to the beginning of the value table
(C0505/3 = 0).

INV_COLLISION_RAN
GE

Relative data model is used
(Lenze setting). The address
pointer has not been
incremented.

Use GDC to create a profile with the absolute data model, load
it into the controller and accept it.

INV_VALUE_RANGE

Attempt to transfer a
non−zero value as the first X
value. The address pointer
has not been incremented.

Enter 0" for the first X value.

C0504/4

Write the Y values in increments with automatic indexing of the address pointer (auto−increment)

INV_LENGTH_RANGE Attempt to write beyond the

data field.

l

Limit the number of writing cycles to the existing number of
interpolation points (see C0391/x).

l

Set the pointer to the beginning of the value table
(C0505/4 = 0).

INV_VALUE_RANGE

The relative data model is
selected.
While writing the Y value,
the representable value
range has been exceeded .

l

Observe the maximum permissible difference between Y
values of

32767 inc.

l

This profile requires a larger number of interpolation points.

C0504/5

Read the X values in increments with automatic indexing of the address pointer (auto−increment)

INV_COLLISION_
RANGE

Attempt to read beyond the
data field.

l

Limit the number of reading cycles to the existing number of
interpolation points (see C0391/x).

l

Set the pointer to the beginning of the value table
(C0505/5 = 0).

C0504/6

Read the Y values in increments with automatic indexing of the address pointer (auto−increment)

INV_COLLISION_
RANGE

Attempt to read beyond the
data field.

l

Limit the number of reading cycles to the existing number of
interpolation points (see C0391/x).

l

Set the pointer to the beginning of the value table
(C0505/6 = 0).

C0505/3

Pointer on X values, selection of an interpolation point on the X axis

INV_LENGTH_RANGE The selected interpolation

point does not exist.

Observe the existing number of interpolation points under
C0391/x.

Advertising
This manual is related to the following products: