Commissioning – Lenze EVS9332xK User Manual

Page 179

Advertising
background image

Commissioning

Basic settings

Entry of motor data

6

6.5

6.5.4

l

6.5−7

EDSVS9332K EN 8.0−07/2013

9300std089

Fig. 6.5−7

"Motor adj" menu of the parameter menu

Procedure

1.

Open the "Parameter menu

® Motor/Feedback ® Motor adj" menu.

2.

Click on C0086 and select the motor whose data corresponds best with the connected
motor.
Note!
The available motors are listed in chapter "Motor selection list".

^ 6.5−9

3.

Click on C0006 and select the motor control operating mode.

4.

Enter the data of the connected motor in the following codes. The data can be found on
the nameplate or the data sheet of the motor.

C0022

Maximum current I

max

of the motor

C0081

Rated motor power

C0084

Stator resistance of the motor
(The setting is only required if the demands on the control characteristics are
very high)

C0085

Leakage inductance of the motor
(The setting is only required if the demands on the control characteristics are
very high)

C0087

Rated motor speed

C0088

Rated motor current

C0089

Rated motor frequency

C0090

Rated motor voltage

C0091

Cos

j.

5.

Save the setting with C0003 = 1.

For non−Lenze motors or
Lenze motors not listed under
C0086