Commissioning – Lenze EVS9332xK User Manual
Page 170
Advertising
![background image](/manuals/566089/170/background.png)
Commissioning
Switch−on sequence
6.3
l
6.3−2
EDSVS9332K EN 8.0−07/2013
Note
Switch−on sequence
14.
Switch on the mains if only the external DC 24 V
supply voltage is switched on.
15.
Enable controller
misc009
59
28
X5
}
Terminal X5/28 = HIGH
(see chapter "Commissioning"
®"Controller inhibit")
16.
Select setpoint
Analog setpoint
selection:
−10 ... +10 V via
potentiometer at X6/1
and X6/2
Fixed speed:
Activate JOG 1 with
X5/E3 = HIGH
JOG 1 is parameterised under C0039/1
17.
The drive should be running now!
CW rotation:
X5/E1 = HIGH and X5/E2 = LOW
CCW rotation:
X5/E1 = LOW and X5/E2 = HIGH
)
Note!
The "Diagnostics" menu provides the possibility to monitor the
most important drive parameters.