Commissioning

Switch−on sequence

6

6.3

l

6.3−2

EDSVS9332K EN 8.0−07/2013

Note

Switch−on sequence

14.

Switch on the mains if only the external DC 24 V
supply voltage is switched on.

15.

Enable controller

misc009

59

28

X5

}

Terminal X5/28 = HIGH
(see chapter "Commissioning"

®"Controller inhibit")

16.

Select setpoint

Analog setpoint
selection:
−10 ... +10 V via
potentiometer at X6/1
and X6/2

Fixed speed:
Activate JOG 1 with
X5/E3 = HIGH

JOG 1 is parameterised under C0039/1

17.

The drive should be running now!

CW rotation:
X5/E1 = HIGH and X5/E2 = LOW
CCW rotation:
X5/E1 = LOW and X5/E2 = HIGH

)

Note!

The "Diagnostics" menu provides the possibility to monitor the
most important drive parameters.