Configuration, Code table – Lenze EVS9332xK User Manual

Page 279

Advertising
background image

Configuration

Code table

8

8.4

l

8.4−5

EDSVS9332K EN 8.0−07/2013

IMPORTANT

Possible settings

Code

Selection

Lenze

Designation

No.

C0054 IMOT

g 0.0

{0.1 A}

300.0 Actual motor current I

mot

MCTRL function block

l

Read only

l

MCTRL−IACT = 100 % = C0022

C0056 MCTRL−MSET2

g −100.00

{0.01 %}

100.00 MCTRL−MSET2 (Mset)

Torque setpoint (output n−controller)

C0057 MAX TORQUE

g 0

{1 Nm}

500 Maximum torque (C86/C22)

Maximum possible torque of the drive
configuration

l

Depending on C0022, C0086

C0058 ROTOR DIFF

−90.0 −180.0

{0.1 °}

179.9 Rotor displacement angle

Zero phase of the rotor for synchronous
motors (C0095)
Is set to −90° when a resolver is selected in
C0025 or C0495.

C0059 MOT POLE NO.

g 1

{1}

50 Number of motor pole pairs

C0060 ROTOR POS

g 0

{1}

2048 Motor rotor position

l

1 rev. = 2048 inc.

C0061 HEATSINK

TEMP

g 0

{1 °C}

100 Heatsink temperature

C0063 MOT TEMP

g 0

{1 °C}

200 Motor temperature

C0064 UTILIZATION

IXT

g 0

{1 %}

150 Device utilisation Ixt

Utilisation of the most recent 180 s

l

C0064 > 100 % releases Trip OC5

l

Trip reset is possible only if C0064 < 95 %

C0064 UTILIZATION

I2XT

g 0

{1 %}

150 I

2

xt motor utilisation

C0067 ACT TRIP

g All fault

messages

à Selection list 10 Error message TRIP

Current fault message

C0070 VP SPEED CTRL

à

0.0

{0.5}

255.0 V

pn

speed controller

à

Depending on C0086

l

Change of C0086 resets value to the
assigned default setting

C0071 TN SPEED CTRL

à

1.0

{0.5 ms}

600.0 T

nn

speed controller

For values > 512 ms the function is
deactivated

à

Depending on C0086

l

Change of C0086 resets value to the
assigned default setting

C0072 TD SPEED CTRL

0.0

0.0

{0.1 ms}

32.0 T

dn

speed controller

C0075 VP CURR CTRL

0.35

0.00

{0.01}

15.99 V

pi

current controller

l

Depending on C0086

l

Change of C0086 resets value to the
assigned default setting

C0076 TN CURR CTRL

1.8

0.5

{0.1 ms}

2000.0 T

ni

current controller

Setting the value 2000 ms deactivates the
function

l

Depending on C0086

l

Change of C0086 resets value to the
assigned default setting

C0077 VP FIELD CTRL

0.25

0.00

{0.01}

15.99 V

pF

field controller

C0078 TN FIELD CTRL

15.0

1.0

{0.5 ms}

8000.0 T

nF

field controller

Setting the value 8000 ms deactivates the
function