Commissioning

Switch−on sequence

6

6.3

l

6.3−1

EDSVS9332K EN 8.0−07/2013

6.3

Switch−on sequence

(

Stop!

When commissioning is completed, do not enable the controller
before

ƒ

CDATA−INIT−NOUT

= LOW when using function block CDATA.

ƒ

CURVEC1−INIT−DFOUT = LOW when using function block
CURVEC1.

Switch−on sequence

Note

1.

Ensure that the controller inhibit is active after
mains connection

misc008

59

28

X5

}

Terminal X5/28 = LOW

2.

Ensure that there is no external error

Terminal X5/E4 = HIGH

3.

Switch on controller

A

The control card is operated via an external voltage
supply:
Switch on the external DC 24 V supply voltage

ON

misc002

B

The control card is operated via the internal voltage
supply:
Switch on the mains. The controller provides the
DC 24 V supply.

4.

The controller is initialised after approx. 2 s

5.

Switch on the PC and start GDC

GDC starts in the online mode if the PC
is connected to the controller.
Information on how to establish a
connection is given in the "Global Drive
Control (GDC) − Getting started"
manual.

6.

Set the machine parameters in GDC

A

Select the basic configuration
Lenze setting: C0005 = 10000 (basic configuration
˜Cam profiler˜)

^ 6.5−2

B

Adapt controller to the mains

^ 6.5−2

C

Enter gearbox and feed constants

^ 6.5−3

D

Enter motor data

^ 6.5−5

E

Set the temperature monitoring of the motor

Motor with PTC or thermal contact:

^ 6.5−17
Motor with KTY:

^ 6.5−18

F

Select the feedback system

^ 6.6−1

7.

Carry out a current controller adjustment if
necessary

^ 6.7−1

8.

Carry out a rotor position adjustment if necessary

^ 6.8−1

9.

Configure the control terminal functions in order to
adapt them to your application.

For internal voltage supply, assign X5/x
with "FIXED1"and X6/x with
"FIXED100%".

^ 6.9−1

10.

Create the motion profile

^ 6.10−1

11.

Save the motion profile

^ 6.10−6

12.

Transfer the motion profile to the controller

^ 6.11−1

13.

Save the settings safe from power failure in one of
the 4 parameter sets (C0003)
With C0003 = 1 the settings are stored in parameter
set 1.

After connecting the DC 24 V supply or
after mains connection, parameter set
1 is activated automatically.
(See chapter "Parameter setting")