Mains choke/mains filter assignment, Wiring of the standard device, 5 mains choke/mains filter assignment – Lenze EVS9332xK User Manual

Page 114

Advertising
background image

Wiring of the standard device

Standard devices in the power range 15 ... 30 kW
Mains choke/mains filter assignment

5

5.5
5.5.5

l

5.5−6

EDSVS9332K EN 8.0−07/2013

Supply conditions

Range

Description

Fuses

l

Only according to UL 248

l

Mains short−circuit current up to 5000 A

rms

: All classes permissible

l

Mains short−circuit current up to 50000 A

rms

: Only classes "J", "T" or "R"

permissible

Cables

l

Only in accordance with UL

l

The cable cross−sections specified in the following apply under the following
conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C

Observe all national and regional regulations!

9300

Rated fuse current

Cable cross−section

Fuse

L1, L2, L3, PE

Type

[A]

[AWG]

Operation with mains choke/mains filter

EVS9327−xK

35

8

EVS9328−xK

60

4

EVS9329−xK

80

4

5.5.5

Mains choke/mains filter assignment

9300

Mains choke

Interference voltage category according to EN 61800−3 and motor cable length

Component

Component

Type

C2

max. [m]

C1

max. [m]

EVS9327−xK

ELN3−0088H035−001

EZN3A0110H030

25

E82ZN22334B230

10

E82ZZ15334B230

1)

10

E82ZN22334B230

50

EZN3B0110H030U

2)

50

E82ZZ15334B230

1)

50

EVS9328−xK

ELN3−0075H045

EZN3A0080H042

25

E82ZN22334B230

10

E82ZN22334B230

50

EZN3B0080H042

50

EVS9329−xK

ELN3−0055H055

EZN3A0055H060

25

E82ZN30334B230

10

E82ZN30334B230

50

EZN3B0055H060

50

1)

RFI filter

2)

Footprint filter

Installation to UL