Configuration, Code table – Lenze EVS9332xK User Manual

Page 299

Advertising
background image

Configuration

Code table

8

8.4

l

8.4−25

EDSVS9332K EN 8.0−07/2013

IMPORTANT

Possible settings

Code

Selection

Lenze

Designation

No.

C0560 FIX SET−VALUE

−199.99

{0.01 %}

199.99 Fixed setpoints

1

100

2

75

3

50

4

25

5

0

...

...

15

0

C0561

s

AIN

1000 FIXED0%

® Selection list 1 FIXSET1

Configuration of analog input signal

C0562

s

® Selection list 2 FIXSET1

Configuration of digital input signals

1 IN1

1000 FIXED0

2 IN2

1000 FIXED0

3 IN3

1000 FIXED0

4 IN4

1000 FIXED0

C0563 (C0561)

g −199.99

{0.01 %}

199.99 FIXSET1

Display of analog input signal

C0564

g

FIXSET1
Display of digital input signals

1 (C0562/1)

... ...

4 (C0562/4)

C0570

s

IN

1000 FIXED0%

® Selection list 1 S&H1

Configuration of analog input signal

C0571

s

LOAD

1000 FIXED0

® Selection list 2 S&H1 LOAD

Configuration of digital input signal

C0572 (C0570)

g −199.99

{0.01 %}

199.99 S&H1

Display of analog input signal

C0573 (C0571)

g

S&H1 LOAD
Display of digital input signal

C0575

1

0

{1 ms}

200 SD8 monitoring

Tripping delay for error message SD8

C0576

100.0

0

0.00

{0.01 %}

100.00 Speed window − nErr−monitoring

Setting the system deviation between actual
speed value and speed setpoint

C0577 VP FLD WEAK

3.00

0.00

{0.01}

15.99 Field weakening controller

Gain V

p

C0578 TN FLD WEAK

50.0

2.0

{0.5 ms}

8192.0 Field weakening controller

Reset time T

n

C0578 = 8000 ms: Switched off

C0579 MONIT NERR

3

0
1
2
3

Trip
Message
Warning
Off

nEEr monitoring
Configuration of monitoring for "system
deviation between actual speed value and
speed setpoint"

C0580 MONIT SD8

3

0
3

Trip
Off

SD8 monitoring
Configuration of monitoring for encoder error
at X8

C0581 MONIT EER

0

0
1
2
3

Trip
Message
Warning
Off

EEr monitoring
Configuration of monitoring for "external
fault"

Advertising
This manual is related to the following products: