Commissioning

Commissioning examples

Multi−axis application

6

6.14

6.14.2

l

6.14−5

EDSVS9332K EN 8.0−07/2013

9300std226

Fig. 6.14−5

"CAN−Master" menu of the parameter menu

Procedure

1.

Change to the "CAN−Master" menu.

2.

Set C0353/2 = 0 (own address C354).

3.

Set a cycle time of 1 ms under C0356/2.

4.

Set C0366 = 0 (no sync response). This reduces the load on the bus.

5.

Set the time interval between two sent sync telegrams under C0369.
Rule of thumb: 5 ms

6.

Configure the CAN output word CAN−OUT2.W1 (low angle) under C864/2 and the CAN
output word CAN−OUT2.W2 (high angle) under C0865/2 .

7.

If possible, locate the function block CAN−OUT2 at the end of the processing table.

8.

Link the output CDATA−X−ACT to the input CAN−OUT2−D1.

9.

Save the settings with C0003 = 1.

Settings for CAN master