Wiring of the standard device

Standard devices in the power range 0.37 ... 11 kW

Mains choke/mains filter assignment

5

5.4

5.4.5

l

5.4−7

EDSVS9332K EN 8.0−07/2013

Supply conditions

Range

Description

Fuses

l

Only in accordance with UL 248

l

System short−circuit current up to 5000 A

rms

: All classes are permissible

l

System short−circuit current up to 50000 A

rms

: Only classes "CC", "J", "T" or

"R" permissible

Cables

l

Only in accordance with UL

l

The cable cross−sections specified in the following apply under the following
conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C

Observe all national and regional regulations!

9300

Rated fuse current

Cable cross−section

Fuse

L1, L2, L3, PE

Type

[A]

[AWG]

Operation without mains choke/mains filter

EVS9321−xK

6

18

EVS9322−xK

6

18

EVS9323−xK

10

16

EVS9325−xK

25

10

Operation with mains choke/mains filter

EVS9321−xK

6

18

EVS9322−xK

6

18

EVS9323−xK

10

16

EVS9324−xK

10

16

EVS9325−xK

25

10

EVS9326−xK

25

10

Max. connection cross−section of the terminal strip: AWG 12, with pin−end connector AWG 10

5.4.5

Mains choke/mains filter assignment

9300

Mains choke

Interference voltage category according to EN 61800−3 and motor cable length

Component

Component

Type

C2

max. [m]

C1

max. [m]

EVS9321−xK

EZN3A2400H002

EZN3A2400H002

5

EZN3B2400H002

50

EVS9322−xK

EZN3A1500H003

EZN3A1500H003

5

EZN3B1500H003

50

EVS9323−xK

EZN3A0900H004

EZN3A0900H004

5

EZN3B0900H004

50

EVS9324−xK

EZN3A0500H007

EZN3A0500H007

5

EZN3B0500H007

50

EVS9325−xK

EZN3A0300H013

EZN3A0300H013

5

EZN3B0300H013

50

EVS9326−xK

ELN3−0150H024−001

EZN3A0150H024

5

EZN3B0150H024

50

Installation to UL