Commissioning

Basic settings

Motor temperature monitoring with KTY

6

6.5

6.5.7

l

6.5−19

EDSVS9332K EN 8.0−07/2013

(

Stop!

Overheating of the motor!
In the Lenze setting, temperature monitoring of the motor is
deactivated (C0583 = 3). The motor temperature in C0063 shows
0 °C even if C0584 = 2 is set.
Possible consequences:

ƒ

The motor can be damaged by a too high motor temperature.

Protective measures:

ƒ

Activate the monitoring of the motor temperature via X7 or
X8 with C0583 = 2 or C0584 = 2.

ƒ

Set C0594 = 2 or 3. Then the connection is additionally
monitored with regard to short circuit and interruption.

ƒ

If you work with several parameter sets, you have to activate
the monitoring separately in each parameter set.

1. Connect monitoring circuit of the motor to X7/8, X7/9 or X8/5, X8/8.

2. Set response of the controller for short circuit or interruption on the

connection (monitoring of the motor temperature has to be activated):
– C0594 = 3: monitoring is switched off.
– C0594 = 0: TRIP error message (keypad display: Sd6

a)

– C0594 = 2: warning signal (keypad display: Sd6

e)

Monitoring with a fixed operating temperature (150 °C)

1. Set response of the controller:

– C0583 = 3: temperature monitoring of the motor switched off.
– C0583 = 0: TRIP error message (keypad display: OH3

a)

– C0583 = 2: warning signal (keypad display: OH3

e)

Monitoring with a variable operating temperature (45...150 °C)

1. Set the operating temperature in C0121.

2. Set response of the controller:

– C0584 = 3: temperature monitoring of the motor switched off.
– C0584 = 2: warning signal (keypad display: OH7

e)

Activation

Adjustment