Commissioning

Current controller adjustment

6

6.7

l

6.7−1

EDSVS9332K EN 8.0−07/2013

6.7

Current controller adjustment

When is a current controller adjustment required?

ƒ The motor data of the motor used is not contained in GDC (e.g. motors

from other manufacturers).

ƒ The application makes high demands on the dynamic performance of

the drive controller (e.g. dynamic positioning, cross cutter).

ƒ The motor/drive controller combination does conform to the standard

power−based assignment. The basic current controller settings only
match for a power−based assignment of the drive controller.

Measure

Setting

Explanation

Reduce maximum
current

Reduce the value in
C0022

With the motor at standstill, the motor
current of the motor phase U is measured
(field frequency 0). This increases the
motor current in the motor phase to
141% and the motor temperature rises
significantly.

Generate maximum
torque setpoint

Connect MCTRL−M−ADD
with FIXED100%

For speed control or position control
(MCTRL−N/M−SWT = 0)

l

Connect
MCTRL−M−ADD with
FIXED100%

l

Connect
MCTRL−N−SET with
FIXED100%

For torque control (MCTRL−N/M−SWT = 1)

Deactivate integral
action component of
current controller

Set C0076 = 2000 ms

The integral action component of the
current controller is deactivated by
setting the reset time T

n

(C0076) to the

longest time. The gain (C0075) remains
unchanged (Lenze setting still valid).

Deactivate quick stop

Set X5/E1 = HIGH or
X5/E2 = HIGH

By preselecting a direction of rotation the
quick stop is deactivated.

Change the operation of
the motor control

Set C0006 = 3

Even if an asynchronous motor is
connected, set the motor control to
’synchronous motor’.

Set the rotor position
setpoint

Set C0058 = −90°

Set the rotor displacement angle to −90°.

Set the actual value
display of the rotor
position to 0° under
C0060

1. Select a TTL encoder

under C0025

2. Save settings with

C0003 = 1

3. If required,

disconnect the
encoder cable at X8

4. Switch off the mains

supply and the
external 24V supply
(if required) and then
on again.

After mains connection C0060 = 0° is
displayed.

Connect the storage
oscilloscope

Put the clamp−on
ammeter around the
motor phase U and
connect it to the
oscilloscope

Oscilloscope settings:

l

Time base: 400

ms/DIV

l

Auto−triggering

Preparations