Configuration, Code table – Lenze EVS9332xK User Manual

Page 277

Advertising
background image

Configuration

Code table

8

8.4

l

8.4−3

EDSVS9332K EN 8.0−07/2013

IMPORTANT

Possible settings

Code

Selection

Lenze

Designation

No.

C0012 TIR (ACC)

0.000 0.000

{0.001 s}

999.900 NSET

Acceleration time T

ir

for the main setpoint of

NSET (referring to speed change 0 ... n

max

)

C0013 TIF (DEC)

0.000 0.000

{0.001 s}

999.900 NSET

Deceleration time T

if

Tif for the main setpoint

of NSET (referring to speed change n

max ...

0)

C0017 FCODE (QMIN)

50

−16000

{1 rpm}

16000 FCODE (Qmin)

Switching threshold n

act

< n

x

n

act

< C0017 activates the comparator output

CMP1−OUT

C0018 FCHOP

1

0
1
2

16/8 kHz
8 kHz sine
16 kHz sine

Switching frequency fchop
Noise−optimised operation with automatic
changeover to 8 kHz

C0019 THRESH

NACT=0

0

0

{1 rpm}

16000 Threshold n

act

=0

Threshold detection at n

act

= 0

C0021 SLIPCOMP

0.00

0.00

{0.01 %}

20.00 Slip compensation

l

Active only for sensorless control below
the value entered under C0291

C0022 IMAX CURRENT

à

0

{0.01 A}

1.50 I

r

I

max

limit current

à

Depending on C0086

l

Change of C0086 resets value to the
assigned default setting (1.5 × Imotor)

C0025

s

FEEDBACK
TYPE

10

Feedback
Input of the encoder specified on the
nameplate of the Lenze motor:
C0025 automatically changes C0420, C0490,
C0495

0

COMMON

C0420, C0490 or C0495 has been changed
subsequently

1

No feedback

Control without feedback system (sensorless
control, SSC)

10

RSx (resolver)

The resolver is labelled with RSxxxxxxxx.
When a resolver is selected, the rotor
displacement angle in C0058 is set to −90°.

110

IT−512−5V

Incremental encoder with TTL level

111

IT−1024−5V

112

IT−2048−5V

113

IT−4096−5V

210

IS−512−5V

SinCos encoder

211

IS−1024−5V

212

IS−2048−5V

213

IS−4096−5V

309

AS−128−8V (SKS)

Single−turn SinCos encoder with RS485
interface from Stegmann

l

Enter the supply voltage under C0421.

310

AS−512−8V (SCS)

311

AS−1024−8V (SRS)

409

AM−128−8V (SKM)

Multi−turn SinCos encoder from Stegmann

l

Enter the supply voltage under C0421.

410

AM−512−8V (SCM)

411

AM−1024−8V (SRM)

C0026

−199.99

{0.01 %}

199.99 FCODE (OffsetAIN)

Freely assignable code for relative analog
signals

l

Used for:
– Offset for terminal X6/1,2
– Offset for terminal X6/3,4

1 FCODE

(OFFSET)

0.00

2 FCODE

(OFFSET)

0.00

Advertising
This manual is related to the following products: