Configuration, Code table – Lenze EVS9332xK User Manual

Page 295

Advertising
background image

Configuration

Code table

8

8.4

l

8.4−21

EDSVS9332K EN 8.0−07/2013

IMPORTANT

Possible settings

Code

Selection

Lenze

Designation

No.

C0470

0

{1}

255 Freely assignable code for digital signals

l

The data words C0470 and C0471 are in
parallel and are identical

0 FCODE 8BIT

DIGITAL

0

1 FCODE BIT 0−7

0

2 FCODE BIT8−15

0

3 FCODE

BIT16−23

0

4 FCODE

BIT24−31

0

C0471 FCODE 32 BIT

0

0

{1}

4294967296 FCODE 32 bits digital

Freely assignable code for digital signals

l

The data words C0470 and C0471 are in
parallel and are identical

C0472 FCODE

ANALOG

−199.99

{0.01 %}

199.99 Freely assignable code for relative analog

signals

1

0.00

2

0.00

3

100.0

0

6

100.0

0

...

...

19

0.00

20

0.00

C0473 FCODE ABS

−32767

{1}

32767 FCODE

Freely assignable code for absolute analog
signals

1

1

2

1

3

0

...

...

9

0

10

0

C0474 FCODE PH

−2147483647

{1}

2147483647 FCODE

Freely assignable code for phase signals
1 rev = 65536 inc

1

0

...

...

10

0

C0475 FCODE PHD

−16000

{1 rpm}

16000 FCODE

Freely assignable code for speed
signals/digital frequency signals

1

0

2

0

3

0

4

0

5

0

C0490

s

FEEDBACK POS

0

Position feedback system
Feedback system for the position controller

0

Resolver at X7

The feedback system can be merged with the
settings of C0495 = 0, 1, 2, 3, 4.

1

Encoder TTL at X8

The selection also sets C0495 to the same
value.

2

Sin encoder at X8

3

Absolute value encoder ST at X8

4

Absolute value encoder MT at X8

Advertising