Motor connection, Wiring of the standard device, Stop – Lenze EVS9332xK User Manual

Page 115

Advertising
background image

Wiring of the standard device

Standard devices in the power range 15 ... 30 kW

Motor connection

5

5.5

5.5.6

l

5.5−7

EDSVS9332K EN 8.0−07/2013

5.5.6

Motor connection

)

Note!

ƒ

Fusing the motor cable is not required.

ƒ

The drive controller features 2 connections for motor
temperature monitoring:
– Terminals T1, T2 for connecting a PTC thermistor or thermal

contact (NC contact).

– Pins X8/5 and X8/8 of the incremental encoder input (X8) for

connecting a KTY thermal sensor.

(

Stop!

Do not use lugs as strain relief.

PE

T1

T2

U

V

W

a

3.4 Nm
30 lb-in

a

0

9300vec131

Fig. 5.5−3

Installation of shield sheet for drive controllers 15 ... 30 kW

0 Fasten the shield sheet with two self−tapping screws Ж 4 Ч 14 mm (a)

Shield sheet installation