Technical data – Lenze EVS9332xK User Manual

Page 40

Advertising
background image

Technical data

General data and operating conditions

3

3.1

l

3.1−2

EDSVS9332K EN 8.0−07/2013

Ambient conditions

Site altitude

< 4000 m amsl
> 1000 m amsl: reduce the rated output current by
5 %/ 1000 m

Mechanical

Vibration resistance EN 50178

EN 61800−5−1
Germanischer
Lloyd, general
conditions

Tested according to "General Vibration Stress
Characteristic 1"

Electrical

AC−mains
connection

Max. mains
voltage range

320 V − 0 % ... 528 V + 0 %

Mains frequency

45 Hz − 0 % ... 65 Hz + 0 %

Power system TT,
TN

Operation permitted without restrictions with
earthed neutral.

Power system IT

Operation only permitted with the device variants
V024 or V100.
Operation permitted without restrictions with
insulated neutral.
Observe instructions on specific measures!

Operation on
public supply
systems

EN 61000−3−2

Limitation of harmonic currents

Total output at the
mains

Compliance with the
requirements

1)

< 1 kW

With mains choke.

> 1 kW

Without additional
measures.

1)

The additional measures mentioned have the effect that solely

the controllers meet the requirements of EN 61000−3−2. The
machine/system manufacturer is responsible for the compliance
with the requirements for the machine/system!

DC−mains
connection

Max. mains
voltage range

450 V − 0 % ... 740 V + 0 %

Operating
conditions

DC voltage must be symmetrical to PE.
The controller will be destroyed when +U

G

or −U

G

are earthed.

Motor connection

Length of the
motor cable

< 50 m
No additional output filters are required at a rated
mains voltage and a switching frequency of 8 kHz.
If EMC requirements have to be met, the
permissible cable length may be affected.

Mounting conditions

Mounting place

In the control cabinet

Mounting position

Vertical

Free spaces
Dimensions
Weights

^ 4−1