Parameter setting – Lenze EVS9332xK User Manual

Page 247

Advertising
background image

Parameter setting

Parameter setting with the XT EMZ9371BC keypad

Changing and saving parameters

7

7.2

7.2.4

l

7.2−5

EDSVS9332K EN 8.0−07/2013

Action

Key
sequence

Step

T y

T z

Quick change of digit

7.

Accept the changed parameter

Display of SHPRG or SHPRG

p T V

Confirm change to accept the parameter
Display "OK"

Display

p −

The parameter has been accepted
immediately

8.

Enable the controller, if
required

U

1)

The drive runs again

9.

Change to the code level

A

V

Display of the operating level

B

V

Display of the code with changed
parameter

10. Change further parameters

Restart the "loop" with step 1. or 3.

11. Save changed parameters

A

z y Z Y

Select the code C0003 "PAR SAVE" in the
menu "Load/Store"

B

V

Change to the parameter level
Display "0" and "READY"

Select the parameter set
in which the parameters
are to be saved
permanently

C

z

Save as parameter set 1:

ð Set "1" "Save PS1"
Save as parameter set 2:

ð Set "2" "Save PS2"
Save as parameter set 3:

ð Set "3" "Save PS3"
Save as parameter set 4:

ð Set "4" "Save PS4"

D

T V

When "OK" is displayed, the settings are
permanently saved in the selected
parameter set.

12. Change to the code level

A

V

Display of the operating level

B

V

Display of C0003 "PAR SAVE"

13. Set parameters for another

parameter set

Restart the "loop" with step 1. or 3.

1)

The function of the

S key can be programmed:

C0469 = 1: Controller inhibit
C0469 = 2: Quick stop (Lenze setting)

Advertising