Configuration

Code table

8

8.4

l

8.4−15

EDSVS9332K EN 8.0−07/2013

IMPORTANT

Possible settings

Code

Selection

Lenze

Designation

No.

C0329 ADAPT ON/OFF

0

PCTRL1 Adaptation On/Off
Activation of process controller adaptation

0

no process controller adaptation
(C0222)

1

PCTRL1−ADAPT + linear characteristic

2

PCTRL1−ADAPT + 3−point characteristic

3

System deviation + 3−point
characteristic

C0332 PCTRL1 TIR

0.000 0.000

{0.001 s}

999.900 PCTRL1

Acceleration time Tir
(referring to setpoint change 0 ... 100 %)

C0333 PCTRL1 TIF

0.000 0.000

{0.001 s}

999.900 PCTRL1

Deceleration time Tif
(referring to setpoint change 0 ... 100 %)

C0336 ACT VP

g 0.0

{0.1}

500.0 PCTRL1

Actual V

p

C0337 BI/UNIPOLAR

0

0
1

Bipolar
Unipolar

PCTRL1
Bipolar/unipolar range of action

C0338 ARIT1 FUNCT

1

0
1
2
3
4
5
15

OUT = IN1
OUT = IN1 + IN2
OUT = IN1 − IN2
OUT = IN1 × IN2
OUT = IN1 / IN2
OUT = IN1 / (100% – IN2)
OUT = IN1 % IN2

ARIT1
Function selection

C0339

s

® Selection list 1 ARIT1

Configuration of analog input signals

1 ARIT1−IN1

1000 FIXED0%

2 ARIT1−IN2

1000 FIXED0%

C0340

g

ARIT1
Display of analog input signals

1 (C0339/1)

2 (C0339/2)

C0350 CAN ADDRESS

1

1

{1}

63 CAN

System bus node address

l

Change becomes effective after ˜reset
node˜ command

C0351 CAN

BAUDRATE

0

0
1
2
3
4

500 kbps
250 kbps
125 kbps
50 kbps
1000 kbps

CAN
System bus baud rate

l

Change becomes effective after ˜reset
node˜ command

C0352 CAN MST

0

0
1

Slave
Master

CAN
Configuration of system bus node

l

Change becomes effective after ˜reset
node˜ command

C0353

0
1

C0350
C0354

CAN
Source for system bus address

1 CAN ADDR

SEL1

0

CAN−IN1, CAN−OUT1

2 CAN ADDR

SEL2

0

CAN−IN2, CAN−OUT2

3 CAN ADDR

SEL3

0

CAN−IN3, CAN−OUT3