Commissioning

Setting the speed feedback
SinCos encoder at X8

6

6.6
6.6.3

l

6.6−2

EDSVS9332K EN 8.0−07/2013

ƒ C0025 = 110, 111, 112 or 113. The number of increments (512, 1024,

2048 or 4096) is set automatically.

The incremental encoder is supplied with voltage by the drive controller.

(

Stop!

If the supply voltage is too high, it may destroy the incremental
encoder.

Under C0421 you can adjust the supply voltage V

CC

(5 V) of the incremental

encoder in order to compensate for the voltage drop along the incremental
encoder cable (if required).

Calculation of the voltage drop

DU [ l [m] @

R [

W]

[m]

@ I

Inc

[A]

l

Length of the incremental encoder cable

R

Resistance of the incremental encoder cable

I

Inc

Current consumption of the incremental
encoder

6.6.3

SinCos encoder at X8

SinCos encoders can be operated at X8. For the wiring diagram and the pin
assignment of X8, please refer to chapter "Wiring of the standard device"

® "Wiring of the feedback system".

(

Stop!

Uncontrolled acceleration of the motor!

ƒ

If the SinCos encoder fails, the motor may accelerate in an
uncontrolled manner.

Protective measures:

ƒ

Activate the monitoring for the SinCos encoder with
C0580 = 0.

ƒ SinCos encoder with 5 V supply voltage:

C0025 = 210, 211, 212, or 213. The number of increments (512, 1024,
2048 or 4096) is set automatically.

ƒ Single−turn SinCos encoder with 8 V supply voltage:

C0025 = 309, 310, or 311. The number of increments (128, 512 or 1024)
is set automatically.

ƒ Multi−turn SinCos encoder with 8 V supply voltage:

C0025 = 409, 410, or 411. The number of increments (128, 512 or 1024)
is set automatically.

ƒ Monitoring (SD8) of the SinCos encoder:

C0580 = 0 (TRIP, Lenze setting)
C0580 = 3 (off)

Activation

Adjustment

Activation