Fuses and cable cross-sections, Fuses and cable cross−sections, Dc−bus operation – Lenze EVS9332xK User Manual

Page 417

Advertising
background image

DC−bus operation

Fuses and cable cross−sections

10

10.3

l

10.3−1

EDSVS9332K EN 8.0−07/2013

10.3

Fuses and cable cross−sections

)

Note!

ƒ

All fuses specified here only have the purpose of
disconnection after a short circuit. For cable protection specific
fuses must be used.

ƒ

In the following tables the rated currents of the Lenze fuses
are listed. If other fuses are used, other fuse currents and cable
cross−sections may result.

ƒ

We recommend using fuse holders with a signalling contact.
Like this, the entire drive system can be switched off
(inhibited) when a fuse fails.

ƒ

Always fuse DC cables using 2 poles (+U

G

, −U

G

).

Supply conditions

Range

Description

Mains

DC 460 ... 740 V

Fuses

l

Only semiconductor fuses.

l

If you are using fuses other than those indicated, other fuse currents and
cable cross−sections may result.

Cables

l

DC cables (+U

G

, −U

G

) must always have two−pole insulation.

l

Laying systems B2 and C: Use of PVC−insulated copper cables, conductor
temperature < 70 °C, ambient temperature < 40 °C, no bundling of cables or
cores, three loaded cores. The information is a recommendation. Other
designs/laying systems are possible (e.g. according to VDE 0298−4).

Observe all national and regional regulations!

Installation in accordance
with EN 60204−1