Motor temperature – Lenze EVS9332xK User Manual

Page 264

Advertising
background image

Configuration

Monitoring
Motor temperature

8

8.2
8.2.7

l

8.2−6

EDSVS9332K EN 8.0−07/2013

8.2.7

Motor temperature

The motor temperature is monitored by means of a KTY. Connect the
thermal sensor to the resolver cable at X7 or the encoder cable at X8.

ƒ Warning threshold (OH7) can be set via C0121

– The switch−on point is 5 °C below the threshold set.

ƒ Fixed warning threshold (OH3) = 150 °C

– The switch−on point is 135 °C.

The response for the case when the thresholds are exceeded can be defined
in:

ƒ C0584 (adjustable threshold)

ƒ C0583 (fixed threshold)

(

Stop!

With the setting C0583 = 3, monitoring is deactivated. The
motor temperature in C0063 shows 0 °C, even if C0584 = 2
(warning) is set.

The SD6 fault is triggered if there is a short or open circuit between X7/8 and
X7/9 or X8/5 and X8/8.

The response can be set under C0594.

The motor temperature is monitored with a PTC thermistor or thermal
contact. Wire the temperature sensor to T1, T2.

ƒ Fixed warning threshold (OH8)

– The switch−off threshold and the hysteresis depend on the

temperature sensor (DIN 44081).

The response to exceeding the threshold can be set under C0585.

(

Stop!

Motor could be destroyed!

ƒ

If the responses "Warning" or "Off" are set, the motor could be
destroyed by overload.

Protective measure:

ƒ

Set the response "TRIP".

KTY at X7 or X8

Monitoring of the KTY at X7
or X8

PTC thermistor or thermal
contact (NC contact) at T1, T2

Advertising
This manual is related to the following products: