Commissioning – Lenze EVS9332xK User Manual

Page 224

Advertising
background image

Commissioning

Transfer of motion profiles
Transfer of profile data from the PLC/IPC to the controller

6

6.11
6.11.4

l

6.11−8

EDSVS9332K EN 8.0−07/2013

Checking the X axis

9300kur033

Fig. 6.11−6

Checking the X axis of the profile

)

Note!

The data for the X axis must be entered in ascending order.
Otherwise the drive may operate incorrectly (e.g. CCR trip) or
execute uncontrolled movements.
The entry of data in X direction is checked with code
C0501/1 = 0:

ƒ

Correct entry: The controller responds with the "ACK"
message.

ƒ

Faulty entry: The controller responds with the
"INV_VALUE_RANGE" message (error number 13). Code
C0501/1 contains the faulty interpolation point. Further error
messages can be found in chapter "Troubleshooting and fault
elimination".

Excerpt from the attribute table

Code

Index

DS

DA

DT

Format

DL

LCM−R

/W

Condition

dec

hex

C0387

24188

5E7C

E

1

FIX32

VD

4

Ra/Wa

C0389

24186

5E7A

E

1

FIX32

VD

4

Ra/Wa

C0390

24185

5E79

A

1

I32

VH

4

Ra/Wa

C0501

24074

5E0A

A

1

FIX32

VD

4

Ra/Wa

C0502

24073

5E09

A

1

I32

VH

4

Ra/W

C0504

24071

5E07

A

6

U32

VH

4

Ra/W

C0505

24070

5E06

A

4

U32

VH

4

Ra/W

C0511

24064

5E00

A

2

FIX32

VD

4

Ra/W

C0512

24063

5DFF

A

2

FIX32

VD

4

Ra/W

C1317

23258 5ADA

E

1

FIX32

VD

4

Ra/Wa CINH

Advertising
This manual is related to the following products: