Wiring of the standard device

Control terminals

Technical data

5

5.8

5.8.7

l

5.8−11

EDSVS9332K EN 8.0−07/2013

Analog inputs, analog outputs

Terminal

Description

Field

Values

X6/1
X6/2

Analog input 1

Voltage range

Level

−10 V ... +10 V

Resolution

5 mV (11 Bit + sign)

Current range

Level

−20 mA ... +20 mA

Resolution

20

m

A (10 Bit + sign)

X6/3
X6/4

Analog input 2

Voltage range

Level

−10 V ... +10 V

Resolution

5 mV (11 Bit + sign)

X6/62

Analog output 1

Level

−10 V ... +10 V

Load capacity

Maximum 2 mA

Resolution

20 mV (9 bits + sign)

Cycle time

1 ms (smoothing time

t = 2 ms)

X6/63

Analog output 2

Level

−10 V ... +10 V

Load capacity

Maximum 2 mA

Resolution

20 mV (9 bits + sign)

Cycle time

1 ms (smoothing time

t = 2 ms)

X6/7

GND1

Reference potential for analog signals
Isolated to X5/39 (GND2)