Wiring of the standard device

Standard devices in the power range 55 ... 75 kW

Motor connection

5

5.7

5.7.6

l

5.7−7

EDSVS9332K EN 8.0−07/2013

5.7.6

Motor connection

)

Note!

ƒ

Fusing the motor cable is not required.

ƒ

The drive controller features 2 connections for motor
temperature monitoring:
– Terminals T1, T2 for connecting a PTC thermistor or thermal

contact (NC contact).

– Pins X8/5 and X8/8 of the incremental encoder input (X8) for

connecting a KTY thermal sensor.

Wire T1, T2 only if the motor is equipped with a PTC thermistor or thermal
contact (NC contact).

ƒ An "open" cable acts like an antenna and can cause faults on the drive

controller.

{

Danger!

ƒ

All control terminals only have basic insulation (single
isolating distance) after connecting a PTC thermistor or a
thermal contact.

ƒ

Protection against accidental contact in case of a defective
isolating distance is only guaranteed through external
measures, e.g. double insulation.

PE U

V

W

T1 T2

+UG -UG

PES

PES

PE

M

3~

J>

PES

PES

PES

2.7 k

MONIT-OH8

15 V

3.3 k

7.4 k

9300vec139

Fig. 5.7−3

Circuit diagram of motor connection with PTC thermistor or thermal contact (NC
contact) at T1, T2

Motor with PTC thermistor or
thermal contact (NC contact)