ƒ The installation and commissioning of the Safe torque off" function

must be carried out by skilled personnel only.

ƒ All safety−relevant cables (e.g. control cable for the safety relay,

feedback contact) outside the control cabinet must be protected, for
instance by a cable duct. Short circuits between the single cables must
be ruled out!

ƒ Wiring of the safety relay K

SR

with insulated wire end ferrules or rigid

cables is absolutely vital.

ƒ The electrical reference point for the coil of the safety relay K

SR

must be

connected with the protective conductor system (DIN EN 60204−1
paragraph 9.4.3). Only this measure guarantees that the operation is
protected against earth faults.