Detecting and eliminating emc interferences, Wiring of the standard device – Lenze EVS9332xK User Manual

Page 96

Advertising
background image

Wiring of the standard device

Basics for wiring according to EMC
Detecting and eliminating EMC interferences

5

5.3
5.3.7

l

5.3−6

EDSVS9332K EN 8.0−07/2013

5.3.7

Detecting and eliminating EMC interferences

Fault

Cause

Remedy

Interferences of
analog setpoints of
your own or other
devices and
measuring systems

Unshielded motor cable

Use shielded motor cable

Shield contact is not extensive
enough

Carry out optimal shielding as
specified

Shield of the motor cable is
interrupted by terminal strips,
switched, etc.

l

Separate components from
other component part with a
minimum distance of 100 mm

l

Use motor choke/motor filter

Install additional unshielded
cables inside the motor cable (e.g.
for motor temperature
monitoring)

Install and shield additional cables
separately

Too long and unshielded cable
ends of the motor cable

Shorten unshielded cable ends to
maximally 40 mm

Conducted
interference level is
exceeded on the
supply side

Terminal strips for the motor
cable are directly located next to
the mains terminals

Spatially separate the terminal
strips for the motor cable from
main terminals and other control
terminals with a minimum
distance of 100 mm

Mounting plate varnished

Optimise PE connection:

l

Remove varnish

l

Use zinc−coated mounting
plate

HF short circuit

Check cable routing