Transfer of motion profiles

Transfer of profile data from the controller to the PLC/IPC

6

6.11

6.11.5

l

6.11−9

EDSVS9332K EN 8.0−07/2013

6.11.5

Transfer of profile data from the controller to the PLC/IPC

EVS9300EK

C0002

CDATA

EEPROM

RAM1

RAM2

C0387

C0003

CDATA-LOAD = HIGH

M

3~

MCTRL

9300kur028

Fig. 6.11−7

Transfer of profile data from the controller to the PLC/IPC (principle)

1. Use C0387 to select whether the profile data in the background data

field or in the active data field of the controller is to be read.

2. Read out the version identifier under C0506/1. Enter the version

identifier in line 1 of the profile data set.

3. Transfer the value "0" to C0505/1. This sets the pointer in the

controller to the beginning of the profile data set.
Then lines 2 to 1242 of the profile data set in C0504/1 are read as 32−bit
values and written to the PLC / the IPC.
The controller must acknowledge each transfer with the ACK" message.
Only then the next data can be requested.

4. Check for correct transmission by using the checksum.

5. Compare the checksum in C0509 with the value in the last line of the

profile data set transferred. For fault−free transmission the two values
are identical.