Comtech EF Data CDM-625A User Manual

Page 628

Advertising
background image

CDM-625A Advanced Satellite Modem

MN-CDM625A

Appendix F

Revision 3

F–22

• If the power changes calculated would put the CnC Ratio out of its working range.

• If the Rx signal level is above its minimum level – if it is not, the CnC Ratio monitor will

not be accurate, which is essential correct calculations.

• If the power change would result in the Eb/No margin on either side becoming negative

(see below).

At the end of the re-balance procedure, the modem will display the result:

• Full re-balance.

• Partial re-balance.

• Some issue was found that prevents a re-balance.

In the case of a partial or no re-balance, the modem displays the reason for this result; you

can then adjust an operating parameter and try again.

CAUTION – READ THESE IMPORTANT NOTES:

You should be aware that after the re-balance has been carried out, it is

very likely that the CnC Ratio will not be at 0dB, and the Eb/No margins will

not be equal. This is particularly true for cases where there is an asymmetry

in antenna size, terminal G/T, symbol rate etc. This is an inherent function

of the re-balancing algorithm, and is not a cause for concern.

You should only attempt to do a re-balance if it is known with certainty

that there are CLEAR SKY conditions at BOTH SIDES OF THE LINK.

It is not necessary that there be a person at each end – the re-balance can

be initiated from either side, with the other side unattended.

Following the re-balance, the CDM-625A stores key parameters, such as Tx Power level, that

are referred to as the Home State. In the event of a loss of communication between the two

sides, the modem will revert to Home State, which is a known safe condition that will not

cause TCP to be exceeded. Once the link conditions have improved so that communication is

re-established, CnC-APC will automatically re-activate.

2)

In the second phase of the algorithm, Eb/No, CnC ratio, and RSL are continuously

monitored. For every combination of the modulation, FEC type and FEC code rate, the

modem calculates an Eb/No margin. An Eb/No margin of 0 dB is arbitrarily determined to

be the Eb/No value that produces a BER of 1 x 10

-7

at the output of the decoder, plus 1 dB.

If the algorithm senses that Eb/No margin is dropping, power is increased at one or both

ends of the link, but in a manner that ensures that TCP is not exceeded. In the vast majority

of cases the TCP during a fade will not exceed its clear-sky value by more than +0.5 dB.

Advertising