Chapter 1: General Installation and Electrical Connection

PC NC Maintenance Manual

1-7

CNC portion, 104W in the servo portion, and 29W in the I/O portion):

Therefore, the above value is within the temperature increase value.

When it exceeds 10

o

C, separate cooling countermeasures must be arranged.

(2) Heat Exchanger Cooling Capacity

Yaskawa can provide heat exchangers where the cooling capacity is insuffi-
cient even with a circulating fan mounted in the enclosure.

The heat generation indicated in the above table is the allowable heat generated
when the internal temperature increase in the enclosure is limited to under
10

o

C.

Table 1.2: Heat Exchangers

Heat Exchanger

Cooling Capacity

External Dimensions (mm)

REX1550

100W /10

o

C

295 width x 890 height x 50 depth

HEATEX02

250W /10

o

C

440 width x 924 height x 50 depth

qe

=

.

k A

∆Τ=

P P

246

6 x 4.16

= 9.9 (

o

C)