The power supply frequency error, An initial charge is defective – Yaskawa YASNAC PC NC Maintenance Manual User Manual
Page 59
PC NC Maintenance Manual
Chapter 4: Troubleshooting
4-38
Cause and measures
15:The power supply frequency error
Error Contents
The power supply frequency excessive deviation (deviation
≥
6% fre-
quency)
Detection Methods
50/60Hz cannot be distinguished because the power supply frequency
was not in 50Hz±6% or 60Hz±6% when main power is supplied (after
the second attempt at turning ON). Or, the frequency was off from
±6% for three cycles continuously after 50Hz/60Hz was recognized.
Cause and measures
16:An initial charge is defective.
Error Contents
The main circuit condenser charge was not completed in the setting
time.
Detection Methods
An alarm process is performed and the gate is blocked (regeneration
operation stop) if there is no difference between VAC and VDC in 60V
or less even if five seconds or more have passed since MC was turned
ON.
Cause Measures
Control power supply (A1, A2) voltage
is low.
Check the control power supply voltage.
Adjust the control power supply voltage within the specification value.
Control power supply overload by servo
unit defect
Remove the connected servo.
Exchange servo unit.
Power circuit fault
Confirm that the control power supply voltage is within the specifica-
tion value.
Exchange the unit or the power circuit module (DC-DC converter).
Combination of unit and PROM is
wrong.
Confirm the unit and the PROM number.
Control card fault
Exchange the unit (exchange control card)
Cause Measures
Main power supply (R, S, T) open phase,
wavy warp, and momentary power failure
Check the power supply ripple.
Check that the power supply is normalized.
Control card fault
Unit exchange (control card exchange)