AL-02:Ground fault

Error Contents

The ground fault current in the inverter output side exceeded the
ground fault detection level (25% of the rated current of the transistor).

Detection Methods

Add three-phase output current (Iu, Iv, Iw) detected by the current
detector. If this addition value exceeds the ground fault detection drive
level, the current is instantaneously intercepted, and the ground fault
detection signal is turned ON.

If the ground fault detection signal has been turned ON, the drive is
stopped and the alarm is displayed.

Cause and measures

AL-04:Main circuit open fuse line

Error Contents

The main circuit fuse has fused.

Detection Methods

Output to the control card formatting the main circuit open fuse line
signal by the gate driver (7CN-5). If the main circuit open fuse line sig-
nal has been turned ON, the current is intercepted and the alarm is dis-
played.

Cause and measures

Cause Measures

Ground fault

Verify there is no short-circuit between inverter I/O ter-
minal and ground.

Insufficient insulation in the motor.

Check the motor. Exchange the motor with a non-
defective one.

Control card fault

Exchange unit (exchange control card)

Cause Measures

Main circuit fuse fusion

Check the main circuit fuse continuity.
Repair the inverter (fuse and transistor)

Control card fault

Exchange unit (exchange control card)