PC NC Maintenance Manual

Chapter 4: Troubleshooting

4-50

AL-11:Main circuit overvoltage

Error Contents

The main circuit DC voltage exceeded the overvoltage setting value
(410V).

Detection Methods

Output to the control card formatting the main circuit AC voltage sig-
nal [VDET] by the gate driver (7CN-41). If VDET exceeded the main
circuit overvoltage detection level [410V], the current is instanta-
neously intercepted, and the main circuit overvoltage detection signal is
turned ON.

If the main circuit overvoltage detection has been turned ON, the drive
is stopped and the alarm is displayed.

Cause and measures

Cause Measures

Power supply voltage is high.

Check the voltage between input terminals.

Power supply voltage is low (regenera-
tive ability decrease by the voltage
reduction).

Change the power supply voltage to the value in the speci-
fication value by the transformer tap changer etc.

Power supply open phase and power
failure

Normalize the power supply.

Motor code improper selection

Confirm control parameter (C1-25) setting and refer to the
setting list.

Control parameter setting is defective.

Refer to the setting list for the control parameters.

The converter selection is defective.

Perform a proper selection (related to servo capacity).

The reactor selection is defective.

Perform a proper selection (corresponded to the converter
capacity).

Control card fault

Exchange unit (exchange control card)

Converter (MR5) error

Exchange unit (exchange converter)