The VS-626M5

PC NC Maintenance Manual

4-151

List Of Inverter Faults

If a fault occurs during operation, protective functions are activated
(depending on the fault) and operation is stopped. The contents of the
faults are displayed on the digital operator (option) in AL codes and on the
7-segment LEDs in numbers.

Fault codes are output as signals to pins 26 ~ 29 of 6CN as shown in the
figure below .

Figure 4.25: Fault Code Output

Fault

No. 22

Name

Contents

Corrective Actions

Built-in MC operation
fault

Magnetic contactor did not func-
tion.

Heat sink overheat 1

Heat sink temperature exceeded
upper limit (minor fault).

Check the ambient temperature for
effective cooling.

Heat sink overheat 2

Heat sink temperature over upper
limit continued for one minute or
longer.

Heat sink thermistor
disconnection

Thermistor for heat sink tempera-
ture detection was disconnected.

Replace the unit.

The ambient temperature is low
[-20

°

C (-4

°

F) or below].

Raise the ambient temperature to
above -20

°

C (-4

°

F).

Control PC board
temperature fault 1

Control PC board temperature
exceeded +80

°

C (176

°

F) (minor

fault).

Check the ambient temperature for
effective cooling.

Control PC board
temperature fault 2

Control PC board temperature
exceeded +85

°

C (185

°

F).

CPU built-in A/D error Built-in A/D converter error

Replace the control PC board.

ROM error

Memory (PROM) error

EEPROM error

Memory (EEPROM) error

CPU error

CPU error

Control PC board
fault

WDT time exceeded.

Table 4.36: Fault Diagnosis and Corrective Actions of Converter (Continued)

Fault Code @ › œ œ ›

6CN Pin 26 (FC0)
6CN Pin 27 (FC1)
6CN Pin 28 (FC2)
6CN Pin 29 (FC3)

(The common pin is pin 30.)