Chapter 4: Troubleshooting

PC NC Maintenance Manual

4-19

(c)

There is no input to handle PG

Check the input voltage (5V) at the handle PG terminal.

Check the handle PG signal cable connector to see if it is
securely plugged in.

(d)

Handle PG is faulty
Verify the following (counter monitor) on the I/O screen if the
values change according to the operation of the pulse handle.
#3037 (No. 1 handle)
#3038 (No. 2 handle)
#3039 (No. 3 handle)

(e)

Other related parameters
Verify the setting for the following parameters.

(3)

Jog Operation is Impossible

(a)

Jog mode signal is not input
Verify the bit status of I/O monitor #3000.
Dl = l
Other bits (DO, D2 to D7) = O

Maximum feedrate for handle operation

Parameter pm2860 (linear axis) Parame-
ter pm2861 (rotary axis)

Acceleration/deceleration time constant

Parameters pm2561 to pm2565

Pulse multiplication ratio of “×100” is set (pm2003
D7 = 1)

Parameter pm2549