Chapter 4: Troubleshooting

PC NC Maintenance Manual

4-39

Cause and measures

23:Integration MC defective performance

Error Contents

The magnetic contactor does not work.

Detection Methods

If answer does not return after 500ms after MC is turning ON, the gate
is blocked (regeneration operation stop), and the alarm is processed.

Cause and measures

43, 44:Heat sink overheating 1 and 2

Error Contents

43: Heat sink temperature exceeded the upper limit. (minor fault)

44: Teosinte temperature exceeded the upper limit and has passed for
one minute or more.

Detection Methods

The voltage for the heat sink temperature detection is consistent with
the thermistor signal (2CN-10) for the heat sink temperature detection.

If the temperature of the heat sink exceeds 80ºC, the minor fault display
is performed due to heat sink overheating 1(43). The drive continues.

The minor fault display is released if the temperature of the heat sink is
79ºC or less.

If the state of heat sink overheating 1(43) continues for one minute, the
gate is blocked (regeneration operation stop), and the alarm is pro-
cessed due to heat sink overheating 2(44).

Cause Measures

MC fault

Confirm that the MC operates within a few seconds after
turning ON.
Exchange MC.

Charging current control resistance
disconnection

Confirm that there is DC generative voltage rising.
Exchange resistance.

Cause Measures

MC fault (coil disconnection/defective
contact)

Confirm that the MC operates within a few seconds after the
second attempt of turning ON.
Exchange MC.

MC answer signal disconnection

Check the connection of the signal conductor.