9 troubleshooting – Yaskawa YASNAC PC NC Maintenance Manual User Manual

Page 170

Advertising
background image

The VS-626M5

PC NC Maintenance Manual

4-149

Parts Replacement Schedule (Guidelines)

Replace the following parts periodically, for a long, safe, trouble-free
working life of the VS-626M5 and VS-656MR5.

Note: Operating conditions are as follows:

Ambient temperature: 30

°

C (86

°

F) yearly average

Load factor: 80% or below
Operation rate: 20 hours or below /day

4.9 Troubleshooting

This chapter describes the inverter and converter fault display, the fault contents
caused by motor malfunctions, and the corrective actions to be taken.

When the VS-626M5 or the VS-656MR5 detects a fault, the fault number is dis-
played on the 7-segment LED, the fault contact output is activated, and the motor
coasts to a stop. Check the cause and take corrective actions.

If the inspections or corrective actions described cannot solve the problem, con-
tact your Yaskawa customer service representative immediately.

To restart, turn ON the reset input signal, depress the RESET key, or shut OFF the
main circuit power supply once to reset the stop status.

Table 4.35: Parts Replacement Schedule

Parts

Interval (Approx.)

Remarks

Inverter/
Converter

Cooling Fan

2 to 3 years

Replace.

Smoothing
Capacitor

5 years

Inspect to determine whether replacement
is required.

Breakers or
Relays

æ

Inspect to determine whether replacement
is required.

Fuse

10 years

Replace.

Aluminum Elec-
trolytic Capacitor
on PC Board

5 years

Inspect to determine whether replacement
is required.

Motor

Bearing

12,000 hours or 2 years

Disassemble and replace worn items or
provide necessary maintenance.

Cooling Fan

15,000 hours or 2 years

Replace the fan.

Overhaul

20,000 hours or 5 years

Contact your Yaskawa customer service
representative.

Advertising