Yaskawa YASNAC PC NC Maintenance Manual User Manual
Page 132
The VS-626M5
PC NC Maintenance Manual
4-111
Notes:
1. Connect using exclusive-use connection bus bar.
2. Wire size is selected assuming external suspended wiring of single 3-core cables at an ambient
temperature of 30
°
(86
°
F).
3. If ambient temperature exceeds 30
°
(86
°
F), allowable current of wire may be lowered.
4. Temperature for each wire indicates maximum allowable conductor temperature.
5. For open chassis type only. Not provided for heat sink externally cooling type.
Table 4.23: 200V Class Inverter Power Cable Specifications
Terminal Symbol
Terminal
Screw
Wire Size
UL-approved 75
(167
°
F)
temperature-rated
copper wire
[AWG (mm
2
)]
600V vinyl-
sheath
insulated wire
(IV, VV) 60
(140
°
F) (mm
2
)
600V
crosslinked
polyethylene
wire (IC) 90
(194
°
F) (mm
2
)
600V rubber-
insulated cabtyre
cable (CT) 60
(140
°
F) (mm
2
)
23P7
P/_, N/_
M6
Note 1
U/T1, V/T2, W/T3
M5
8 (8.4)
5.5
3.5
5.5
M5 ~ 2
10 (5.3)
3.5
2
3.5
25P5
P/_, N/_
M6
Note 1
U/T1, V/T2, W/T3
M5
8 (8.4)
5.5
3.5
5.5
M5 ~2
10 (5.3)
3.5
2
3.5
27P5
P/_N, N/_
M6
Note 1
U/T1, V/T2, W/T3
M5
8 (8.4)
8
3.5
8
M5 ~2
8 (8.4)
5.5
3.5
5.5
2011
P/_, N/_
M6 ~ 2
Note 1
U/T1, V/T2, W/T3
M8
6 (13.3)
14
8
14
M6 ~ 2
8 (8.4)
8
5.5
5.5
2015
P/_, N/_
M6 ~ 2
Note 1
U/T1, V/T2, W/T3
M8
4 (21.2)
22
14
22
M6 ~ 2
6 (13.3)
14
8
8
2018
P/_, N/_
M6 ~ 2
Note 1
U/T1, V/T2, W/T3
M8
3 (26.7)
30
14
30
M6 ~ 2
6 (13.3)
14
8
14
2022
P/_, N/_
M6 ~ 2
Note 1
U/T1, V/T2, W/T3
M8
2 (33.6)
50
22
38
M6 ~ 2
6 (13.3)
14
8
14
2030
P/_, N/_
M6 ~ 2
Note 1
U/T1, V/T2, W/T3
M8
2/0 (67.4)
80
38
80
M6 ~ 2
4 (21.2)
22
14
14
2037
P/_, N/_
M6 ~ 4
Note 1
U/T1, V/T2, W/T3
M10
3/0 (85)
100
50
100
M8 ~ 2, M6
3 (26.7)
22
14
22
2011 to
2030
A12/r2, A22/t2
(Note 5)
M4
14 (2.1)
2
2
2