Chapter 4: Troubleshooting

PC NC Maintenance Manual

4-75

The motor reverses

Cause and measures

The motor does not rotate at the command speed.

Cause and measures

The acceleration/declaration time is long.

Cause and measures

Cause Measures

Main circuit and motor encoder signal conduc-
tor improper connection

Check wiring according to the interconnecting wir-
ing chart.

Cause Measures

Speed command signal error

Check the speed command by the drive state display function
(U1-02).
Readjust the host speed command function.

Motor rated speed improper setting

Confirm the control parameter (C1-26) setting and refer to the
setting list.

Motor speed adjustment is defective.

Check the motor speed by the drive state display function
(U1-01).
Adjust the motor speed by the control parameter (C1-12)
(Refer to P157).

Speed control is P control

Check whether the PPI signal is not inputted by the drive
state display function (U1-09).

Torque control drive

Check whether neither external torque limit signal TLL nor
TLH are inputted.

Control card fault

Exchange unit (exchange control card)

Cause Measures

Software starting time setting is
defective. (Setting time is long)

Confirm the control parameter (C1-10) setting and refer to the
setting list.

Motor code improper selection

Confirm the control parameter (C1-25) setting and refer to the
setting list.

Torque control drive

Check whether neither external limiting torque signal TLL nor
TLH are input.

Load machine overload

Check the load state for the load factor meter state to examine
the load machine loss and inertia moment, etc.
Raise the drive capacity of the inverter and the motor.

Control card fault

Exchange unit (exchange control card)