Chapter 4: Troubleshooting

PC NC Maintenance Manual

4-57

AL-43, -44: Heat sink overheating 1 and 2

Error Contents

AL-43: The heat sink temperature exceeded the upper limit.

AL-44: The heat sink temperature exceeded the upper limit for one
minute or more.

Detection Methods

The heat sink temperature detection voltage is consistent from ther-
mistor signal (7CN-39) for the heat sink temperature detection.

If the heat sink temperature exceeds the heat sink overheating detection
level (determined by the inverter capacity), a minor fault display is per-
formed due to heat sink overheating 1(AL-43). The drive continues.

If the state of heat sink overheating continues for one minute, the cur-
rent is intercepted due to heat sink overheating 2(AL-44).

Cause and measures

Cause Measures

Inverter overload

Check the heat sink temperature by the drive state display (U1-13:
heat sink temperature).

Inverter cooling fan fault

Turn ON the power and check that the motor cooling air is normal.
Exchange the inverter cooling fan.

Heat sink cooling ability
decrease

Check neither the heat sink dust nor oil, etc. adhere.

Thermistor signal conductor
short-circuit

Check heat sink thermistor signal conductor wiring.

Control card fault

Exchange unit (exchange control card)