APPLICATIONS

2.6.6 Mode Switch cont.

— 2-56 —

Using Error Pulse as a Detection Point of Mode Switch

Error pulse can be used for position control only.

If an error pulse exceeds the value set in parame-
ter Cn-0F, the speed loop switches to P control.

• Example of Use:

The mode switch is used to reduce settling time.
Generally, speed loop gain must be increased to reduce settling time. Using the mode
switch suppresses the occurrence of overshoot and undershoot when speed loop
gain is increased.

Without mode switch

Motor

speed

Speed reference

Motor speed

Settling time is long

Increase speed loop gain

Without mode switch

Motor

speed

Overshoot

Undershoot

Time

Motor speed

Suppress the occurrence

of overshoot and

undershoot.

With mode switch

Settling time

Parameters

The parameters required to set each mode switch are summarized as follows.

Cn-01Bit B

Mode Switch ON/OFF

Factory

Setting: 0

For Position Control

This parameter is used to enable or disable the mode
switch function.

Setting Meaning

0

Uses the mode switch function

1

Does not use the mode switch function

The Servopack allows use of four different types of
mode switch. To select a mode switch, set bits C and D
of memory switch Cn-01.

Cn-01 Bit C

Mode Switch Selection

Factory

Setting: 0

For Speed/Torque Control

and Position Control

Cn-01 Bit D

Mode Switch Selection

Factory

Setting: 0

For Speed/Torque Control

and Position Control

2

Positions

Speed

Speed reference

Motor

speed

Error

pulse

PI control

P control

PI control

Positions

Speed Reference

Actual

motor

operation

Time

Settling time

Mode switch is used to reduce settling

time and suppress undershoot when the

motor stops. It switches PI control to P

control when certain conditions are met.