3.2Applications
— 3-25 —
3.2.6 Clearing Alarm Traceback Data
The following procedure is used to clear the alarm history, which stores the alarms occurring
in the Servopack. Each alarm in the alarm history is set to A.99, which is not an alarm code.
Refer to 3.2.1 Operation in Alarm Traceback Mode for details.
Use the following procedure to clear the alarm traceback data.
1) Press
DSPL
SET
to select the parameter set-
ting mode.
2) Select the parameter number Cn-00.
(Parameter Cn-00 is selected when the
power is turned ON.)
Press the
and
keys to select the digit.
Press the
and
keys to change the
value.
3) Press
DATA
ENTER
to display the current data for
the parameter Cn-00.
4) Press the
and
keys to change the
data to 02.
5) Press
DSPL
SET
to clear the alarm traceback
data.
6) Press
DATA
ENTER
to return to the parameter data
display.
3
Setting Mode
Parameter Number
Data
Set to 00-02.
keys to change the
value.
Press the
Clear the alarm traceback data.
Parameter Number
Data