2 wiring for noise control – Yaskawa Sigma Mini User Manual

Page 113

Advertising
background image

2.8Special Wiring

— 2-69 —

2.8.2 Wiring for Noise Control

Example of Wiring for Noise Control

This Servopack uses high-speed switching elements in the main circuit. It may receive
“switching noise” from these high-speed switching elements if wiring or grounding around the
Servopack is not appropriate. To prevent this, always wire and ground the Servopack correct-
ly.

This Servopack has a built-in microprocessor (CPU). To protect the microprocessor from ex-
ternal noise, install a noise filter in place.

The following is an example of wiring for noise control.

Noise filter

*

Servomotor

Servopack

(Casing)

• Operation relay sequence

• Signal generation circuit

(provided by customer)

Wire with a thickness of

3.5 mm

2

or more

Ground plate

Ground: One-line ground (ground to 100 Ω or less)

(Casing)

(Casing)

(see note 2)

(Casing)

(Casing)

100 or

200 VAC

3.5 mm

2

or more

3.5 mm

2

or more

CN2

CN1

AC/DC

power

supply

2 mm

2

or more

3.5 mm

2

or more

CN2

U

V

W

PG

M

* When using a noise filter, always observe the following wiring instructions:

Note

1) For a ground wire to be connected to the casing, use a thick wire with a thickness of at

least 3.5 mm

2

(preferably, plain stitch copper wire).

2) For wiring indicated by , use twisted-pair cable whenever possible.