2.7Designing a Protective Sequence

— 2-65 —

Preset value: Cn-22 (speed coincidence signal output width)

Set the following parameter to specify the output conditions for speed coincidence signal out-
put.

Cn-22

VCMPLV Speed Coincidence

Signal Output Width

Unit:

min

−1

Setting

Range: 0

to 100

Factory

Setting:

10

For

Speed/Torque

Control

Set the output conditions for speed coincidence signal
/V-CMP.

The /V-CMP signal is output when the difference be-
tween the reference speed and actual motor speed is
not greater than the preset value.

Example: When preset value is 100 and reference
speed is 2000 min

−1

.

/V-CMP is ON (circuit between CN1-8 and CN1-3 is closed) when the speed is between 1900
and 2100 min

−1

.

2.7.5 Running Output Signal

This section describes how to wire and use contact output signal /TGON as a running output
signal. This signal indicates that a Servomotor is currently running.

CN1-8

CN1-3

/TGON

SG-COM

+24 V

Photocoupler output
Maximum operating voltage

per output: 30 VDC
Maximum output current

per output: 50 mA DC

Servopack

I/O power supply

0 V

Output /TGON CN1-8

Running Output (Torque Limit

Output)

For Speed/Torque

Control and

Position Control

This output signal indicates that the motor is currently
running.

It is used as an external interlock.

2

Motor

speed

Reference

speed

/VCMP is output

within this range

Motor

speed

/TGON