2.1Setting Parameters According to Machine Characteristics

— 2-7 —

Output Signal for Torque Restriction Function

The torque restriction function

outputs the signal shown on

the right.

/CLT

Status indication mode bit data

Monitor mode Un-05 bit 4

Parameter Setting:

Cn-2C = 4

Examples of Use:

D

Forced stopping

D

Holding workpiece by robot

Cn-18

CLMI

Forward/Reverse

External Torque Limit

Unit:

%

Setting

Range: 0 to

Maximum

Torque

Factory

Setting:

100

For Speed/Torque

Control and Position

Control

Sets a torque limit value when torque is to be restricted by external contact input.

This function is valid when bit 2 of memory switch Cn-02 is set to 0.

Using /CL Signal

This section describes how to use input signal /CL as torque limit input signals.

I/O power supply

Servopack

+24VIN

/CL

CN1-9

CN1-*1

Host controller

5mA

+ 24 V

Photocoupler

4.7kΩ

Input /CL CN1-*1

Forward/reverse External

Torque Limit Input

For Speed/Torque

Control and

Position Control

These signals are for forward and reverse exter-
nal torque (current) limit input.

This function is useful in forced stopping.

The signal shown on the right is output while
torque is being restricted.

2

Output Signal for Torque

Restriction Function

• /CLT
• Status indication mode bit data

• Monitor mode Un-05 bit 4

• Parameter Setting:

Cn-2C = 4